High Pressure Steam Conditioning Valve DCE

Function


 Pressure and temperature control

Application


 High pressure turbine Bypass without safety function for starting up or stopping steam boilers, respectively
 Steam transfer in case of turbine failure
 Steam conditioning for process steam lines

Design


 
Construction:
angular/Z-form
 
Seat-Ø:
28- 200 mm
 
Capacity:
K-values from 8 m3/h until 800 m3/h
 
Injection:
secondary atomized steam injection or controlled pressure atomizing or spindle injection with atomized steam
 
Throttling:
controlled/uncontrolled
 
Actuator:
hydraulic, electrical or pneumatic
 
Characteristic:
linear/equal percentage
 
Body:
forged, materials and pipe connection in accordance with customer specification
 
Leakage rate:
DIN 3230 part 3 - leakage rate 1
as well as ANSI/FCI 70-2
Class V possible
 
Mounting position:
vertical, horizontal and hanging

 