High Pressure Steam Conditioning Valve with Safety Quick Closing DDE

Function


 Pressure and temperature control
 Safety shut-off function for secondary systems

Application


 High pressure turbine Bypass with safety function for starting up or stopping steam generators, respectively
 Steam transfer in case of turbine failure
 Steam conditioning for process steam lines

Design


 
Construction:
angular/Z-form
 
Seat-Ø:
28- 200 mm
 
Capacity:
K-values from 8 m3/h until 800 m3/h
 
Injection:
secondary atomized steam injection, controlled pressure atomizing
 
Actuator:
hydraulic or pneumatic
 
Characteristic:
linear/equal percentage
 
Body:
forged, materials and pipe connection in accordance with customer specification
 
Leakage rate:
DIN 3230 part 3 - leakage rate 1
as well as ANSI/FCI 70-2
Class V possible
 
Mounting position:
vertcal, horizontal and hanging
 
Steam filter:
for SAV-function (3mm hole diameter)

 